You are here

  • English
  • Magyar
  • Slovenčina

KÖF-C-9002/3 Phase clamp

The KÖF-C-9002/3 phase clamp can be built in or can be
connected to various operating rods and with copper wire
we can get an earthing/short-circuiting device. The
short-circuiting device can be used for short-circuiting of
rail or wire structured bus bars of transformer stations and
power plants.

KÖF-C-9002/3 Phase clamp
 
EN 61230

Thermic limit current
For rail
20 kA/1 s

For wire
20 kA/1 s

Dynamic limit current
For rail
50 kA

For wire
50 kA

Gripping capacity
Ø60x10 mm rail

Ø30 mm stud

Product code
a: 521522

b: 521523

c: 521524

d: 521525

 
 
 

 
 
 

 
 
 

 
 

 
 

 

 
 

 

 

 

Recommended products

VK-RB-2006-H

Thermic limit current
18 kA/2 s

Dynamic limit current 
45 kA/1 s

Gripping capacity
Ø5-30 mm

Product code
522780

VK-RB-2006 Phase clamp

Thermic limit current
18 kA/2 s

Dynamic limit current
45 kA/1 s

Gripping capacity
Ø5-30 mm

KÖF-C-9001 Phase clamp

The KÖF-C-9001 phase clamp can be built in or can be
connected to various operating rods and with copper
wire we can get an earthing/short-circuiting device. The

VK-E-1500/K

-One section operating rod, type VK-E-1500
(rated voltage of the rod 35 kV)
'-Spherical switching head
'-Earthing clip
'-Wire with cross section of 6 mm²

KÖF-C-9000

The earthing short-circuiting device is suitable for earthing/short circuiting different capacitor banks.The set can be assembled from the necessary number of flexible

VK-25-70316

The VK-25-70315 and 70316 earthing rod equipment is for earthing 25 kV overhead line traction systems. The clamps of earthing devices have torque limiter.

2048 ball stud

2048 ball stud

Thermic limit current
40 kA/0,5 s

Thread size
M12

Ball diameter
Ø20 mm